SOUNDNESS TEST
OBJECT
To determine
the soundness of the cement.
APPARATUS
Le-chatelier apparatus, thermometer, trowel, stopwatch, oven, scale.
Fig:-Showing Le-chatelier apparatus
PROCEDURE
- Wt. 100 gm
cement in the pan.
- Now add
water (.78 of the consistency) & make a homogeneous paste.
- Now place
le-chatelier mould on a glass plate & filled by the cement Paste &
covered at top by another glass plate.
- The whole
assemble is submerged in the water about 24 hr. at a temperature between
24 to 35◦C.
- The
distance between the indicators is noted (d1).
- The mould
is again placed in water and heat is applied in such a way that the
boiling point of water is reach in about 30 minutes. The boiling is
continue till one hour.
- The mould
is removed from water and it is allowed to cool down the distance between
the point of indicator is measured d2.
CALCULATIONS
Soundness/expansion of cement = L1-L2
L1=Measurement taken
after 24 hours of immersion in water at a temp. of 27 ± 20 C
L2=Measurement taken
after 3 hours of immersion in water at boiling temperature.
Calculate the mean of two values to
the nearest 0.5 mm.
§ Note::In the event of cement failing
to comply with the specified requirements, a further test should be made from
another portion of the same sample in manner described above, but after aeration (done by spreading out
to a depth of 75 mm at a relative humidity of 50 to 80% for a total period of 7
days).
RESULT
The expansion (d2-d1)
is not more than 10 mm.
PRECAUTIONS
§ All the measurements should be done accurately.
§ Do not apply extra pressure while filling the moulds.
§ During boiling water level should not fall below the height
of the mould.